NOVEC1230 fire extinguishing

NOVEC 1230® automatic fire-extinguishing systems ensure a quick and clean process, without releasing any kind of residue into the area of use: after the fire-extinguishing agent is discharged, it can be removed from the protected space through simple ventilation, allowing normal operations to resume quickly.

By activating sensors that detect a fire in its initial phase, even before the human eye can see the flames, the system releases the extinguishing liquid in the protected area, which is contained in tanks pressurised with nitrogen, which evaporates upon release and spreads evenly throughout the room, totally saturating the environment (total flooding).

The adoption of an automatic NOVEC 1230® system makes it possible to use a new generation of fire-extinguishing agent that is clean, non-toxic, fast, effective, and environmentally friendly.

A sufficient number of cylinders, determined by the correct calculation made by the designer, a distribution network, and dispensing nozzles are the distinctive features common to all systems of this type.

In order to ensure their effectiveness, it is essential that the checks required by the standards, which detail all the activities and maintenance schedules, be performed by specialised personnel.

Faro is the right pratner!

  • Expertise: we know the standards and propose the right solution
  • Reliability: we test all the products we offer
  • Care for the environment: we know how to handle waste and have developed a system of circular economy and reuse
The FARO Team

  • Our technicians receive continuous professional training
  • Our staff are direct employees, not subcontracted
  • We are very well acquainted with multi-site industrial, logistics, and retail operations
FARO is always there

  • Technical service on call 24 hours a day, 7 days a week
  • Direct phone support provided by our operators
  • Expert advice on all regulatory updates

Maintenance phases and frequency

Phase Frequency Situation
Initial inspection - Assumption
(responsible company)
Occasional Before delivery of a new or modified system or when assuming the maintenance of a system
Monitoring
(internal)
Continuous According to the maintenance plan scheduled by the system manager
Routine maintenance
(responsible company)
At least every 6 months According to the scheduled maintenance plan
Extraordinary maintenance
(responsible company)
Occasional According to need for major repairs
Scheduled testing
(responsible company)
At least every 10 years According to regulatory and statutory requirements for testing

Documentation to be acquired prior to starting maintenance activities

  • User and maintenance manual;
  • As-built designs and documentation of the system;
  • Manufacturers' test procedure;
  • Test equipment;
  • Electronic instruments suitable for the tests to be performed.

Initial inspection

To be performed by the Maintenance Technician

Preliminary Inspection
  • Verification that the system corresponds to the executive plan; Installation in conformity with the standard;
  • Visual inspection of the system;
  • Checking the cylinders and related calculations.
Functional Check
  • Verification that the system logics correspond to the project requirements and the operating documents as well as the user and maintenance manual;
  • In the presence of other interconnected systems (active or passive protection or technological systems), check that the system logics are consistent with the project requirements.

Monitoring

To be completed by the Assigned personnel

What?
  • Visual inspection;
  • Checking the status messages on the control unit;
  • Checking the condition of cylinders, nozzles, goosenecks, etc., at least monthly.
When?
  • Daily, weekly, monthly depending on the type of check to be carried out and the size of the system.
Increase frequency in the case of:
  • Installations in environments with a high density of personnel;
  • Installations in environments with frequent temperature changes;
  • Installations in environments with high humidity or presence of vapours;
  • Specific requirements of the manufacturer or designer.

Periodic inspection

To be performed by the Maintenance Technician

What?
  • Check that the initial inspection documents are on hand;
  • Check that no actions have been taken or structural changes made in the protected environment;
  • Verification of the state of the system.
How?
Conventional systems:
-
100% testing of devices
Analogue Systems:
0-6 years
Over a period of 12 months a functional check must be performed on 50% of all devices in all detection zones (twice per year)
7-12 years
Over a period of 12 months a functional check must be performed on 100% of all devices (twice per year)
beyond 12 years
After 12 years the system must undergo a general review

General system check

To be performed by the Maintenance Technician

When?
  • At least once every 12 years.
What?
  • Verification of the availability of spare parts;
  • Verification that the system has not changed (if substantial modifications have been made, the technical documentation must be acquired in the new as-built configuration).
How?
  • Factory overhaul;
  • Replacement with new detectors;
  • Execution of physical test.