Maintenance phases and frequency
Phase | Frequency | Situation |
---|---|---|
Initial inspection - Assumption (responsible company) |
Occasional | Before delivery of a new or modified system or when assuming the maintenance of a system |
Monitoring (internal) |
Continuous weekly and monthly |
According to the scheduled maintenance plan, the correct functioning of the sprinkler system must be tested as specified by the manufacturer and the standard |
Routine maintenance (responsible company) |
Trimestrale Every six months |
According to the scheduled maintenance plan |
Extraordinary maintenance (responsible company) |
Occasional | According to need for major repairs |
Water supply test | Annual | According to regulatory requirements |
Third-party inspection | Annual | Carried out by the responsible person. It should assess whether the system is in compliance with the standard, whether maintenance is adequate, and whether it is commensurate with the inherent risk. |
Check and repair of tanks and valves | Every three years | According to regulatory requirements and in connection with the pumping station |
Cleaning the water reserve | Every ten years | According to regulatory requirements and in connection with the pumping station |
Documentation to be acquired prior to starting maintenance activities
- User and maintenance manual;
- Testing and installer document;
- Product sheet;
- System and electrical panel connection sheet;
- As-built designs and documentation of the system;
- Manufacturers' test procedure;
- Test equipment.